| Plan Review Notes For Permit 00100489 |
| Permit Number |
00100489 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SINK SHALL COMPLY W/FACBC SECS.4.24.1- | | | 4.24.7. | | | | | | 2)DOOR OF TOILET ROOM SHALL NOT SWING | | | INTO THE CLEAR FLOOR REQD.FOR SINK. | | | FACBC SEC.4.22.2 | | | | | | 3)SHOW REQD.CLEAR FLOOR SPACE FOR SINK | | | ON PLAN. | | | | | | 4)SHOW WATER SUPPLY TO SINK ON WATER | | | RISER. | | | | | | 5)TOILET ROOM SHALL BE ACCESSIBLE TO | | | PATRONS.SEE ATTACHED. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|