2001-01-08 00:00:00PROVISO:
 1.PLEASE PROVIDE LETTER DETAILING
 ATTACHMENT OF AHU TO CEILING AND C/U TO
 EQUIPMENT RACK ON ROOF
 2.1997 SMC 304.4.1 REQUIRES THE OPENING
 AND PASSAGEWAY TO BE AT LEAST AS LARGE
 AS THE LARGEST PIECE OF THE EQUIPMENT
 AND IN NO CASE LESS THAN 22 X 36 INCHES.
 3.A MINIMUM OF 18" CLEARANCE IS REQUIRED
 BETWEEN THE ROOF SURFACE AND THE BOTTOM
 OF THE SUPPORT STRUCTURE OF THE EQUIPMEN