| Plan Review Notes For Permit 00100489 |
| Permit Number |
00100489 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.PLEASE PROVIDE LETTER DETAILING | | | ATTACHMENT OF AHU TO CEILING AND C/U TO | | | EQUIPMENT RACK ON ROOF | | | 2.1997 SMC 304.4.1 REQUIRES THE OPENING | | | AND PASSAGEWAY TO BE AT LEAST AS LARGE | | | AS THE LARGEST PIECE OF THE EQUIPMENT | | | AND IN NO CASE LESS THAN 22 X 36 INCHES. | | | 3.A MINIMUM OF 18" CLEARANCE IS REQUIRED | | | BETWEEN THE ROOF SURFACE AND THE BOTTOM | | | OF THE SUPPORT STRUCTURE OF THE EQUIPMEN |
|