Plan Review Notes
Plan Review Notes For Permit 00100488
Permit Number 00100488
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PLUMBING PLAN REVIEWPROVISO
 PREVIOUS COMMENTS NOT ADDRESSED.
 (1) SHT A2-SINK TO COMPLY W/ FACBC
 SEC 4.24.1 NO HIGHER 34" ABOVE FF.
 SEC 4.24.1 KNEE CLEARANCE 27" HIGH.
 30" WIDE, 19" DEEP,SHALL BE PROVIDED.
 SEC. 4.24.5 CLEAR FLR SPACE 30" X 48".
 (2) SEC 4.1.3 (16) (A) SIGNAGE H/C.
 (3) SHT MP-1 AIR CHAMBERS SEC 607.8.3
 TO BE ACCESSIBLE, RECHARGEABLE.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096 X 8233