| Plan Review Notes For Permit 00100488 |
| Permit Number |
00100488 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. LETTER FROM ENGINEER DETAILING | | | ATTACHEMENT OF C/U TO STAND AND AHU TO | | | CEILING TO FOLLOW PRIOR TO INSPECTION | | | ON EQUIPMENT | | | 2. MINIMUM CLEARANCE BETWEEN ROOF SURFAC | | | AND BOTTOM OF SUPPORT STRUCTURE OF EQUIP | | | STAND IN 18". | | | 3. 250 CFM SUPPLY AIR SHOWN ON RETURN | | | SIDE OF AHU IS RETURN AIR NOT SUPPLY | | | PER D. ROMCKE |
|