2001-01-08 00:00:00PROVISO:
 1. LETTER FROM ENGINEER DETAILING
 ATTACHEMENT OF C/U TO STAND AND AHU TO
 CEILING TO FOLLOW PRIOR TO INSPECTION
 ON EQUIPMENT
 2. MINIMUM CLEARANCE BETWEEN ROOF SURFAC
 AND BOTTOM OF SUPPORT STRUCTURE OF EQUIP
 STAND IN 18".
 3. 250 CFM SUPPLY AIR SHOWN ON RETURN
 SIDE OF AHU IS RETURN AIR NOT SUPPLY
 PER D. ROMCKE