Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:PLEASE NOTE THAT THE AIC RATING
 FOR BRKRS INSATLLED IN PANEL SHOWS
 THEM AT 10,000A. THIS IS FINE BUT NO
 AIC RATINGS WERE SUBMITTED FOR MAIN
 DISCONNECT. PLEASE SUBMIT AIC RATING FOR
 MAIN DISC. PLANS WOULD HAVE PASSED WITH
 PROVISO BUT WERE COMING BACK FOR OTHER
 COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372