| Plan Review Notes For Permit 00100488 |
| Permit Number |
00100488 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE:PLEASE NOTE THAT THE AIC RATING | | | FOR BRKRS INSATLLED IN PANEL SHOWS | | | THEM AT 10,000A. THIS IS FINE BUT NO | | | AIC RATINGS WERE SUBMITTED FOR MAIN | | | DISCONNECT. PLEASE SUBMIT AIC RATING FOR | | | MAIN DISC. PLANS WOULD HAVE PASSED WITH | | | PROVISO BUT WERE COMING BACK FOR OTHER | | | COMMENTS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|