| Plan Review Notes For Permit 00100482 |
| Permit Number |
00100482 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | NOTES FROM FIRST REVIEW, NOT ALL WERE | | | ADDRESSED. | | | | | | 1)NOTE: PLEASE SUBMIT AIC RAATINGS FOR | | | ALL NEW EQUIPMENT. MAINS AND PANELS ARE | | | TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. SAYING THE PANEL/MAIN IS AIC | | | RATED DOES NOT GIVE THE RATING. ALL | | | EQUIPMENT HAS DIFFERENT RATINGS FOR | | | DIIERENT FAULTS. PLEASE CONTACT FPL | | | AND CALL IF ANY QUESTIONS. | | | | | | 2)NOTE: PLEASE SEE LOADS SHOWN ON PANEL | | | SCHEDULE. LOADS FAR EXCEED THE RATINGS | | | OF 80% OF BRKR.384-16 | | | LOADS SHOWN AT 2.5KW,1.8KW AND 1.5KW | | | ON 15A AND 20A BRKRS. | | | | | | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | | SHOWS ALL WIRING TO BE IN CONDUIT.??? | | | PLEASE VERIFY AND CHANGE IF NESS. | | | | | | 4)NOTE: PLEASE SEE MISSING OUTLETS PER | | | 210-52 2` OF WALL IN BEDROOMS, 2,3,4. | | | | | | 5)NOTE: PLEASE NOTE MISSING GFI OUTLET | | | FOR A/C EQUIPMENT OUTSIDE. PER 309.1 | | | OF MECH CODE | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 ETX 8372 |
|