Plan Review Notes
Plan Review Notes For Permit 00100482
Permit Number 00100482
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 NOTES FROM FIRST REVIEW, NOT ALL WERE
 ADDRESSED.
  
 1)NOTE: PLEASE SUBMIT AIC RAATINGS FOR
 ALL NEW EQUIPMENT. MAINS AND PANELS ARE
 TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT. SAYING THE PANEL/MAIN IS AIC
 RATED DOES NOT GIVE THE RATING. ALL
 EQUIPMENT HAS DIFFERENT RATINGS FOR
 DIIERENT FAULTS. PLEASE CONTACT FPL
 AND CALL IF ANY QUESTIONS.
  
 2)NOTE: PLEASE SEE LOADS SHOWN ON PANEL
 SCHEDULE. LOADS FAR EXCEED THE RATINGS
 OF 80% OF BRKR.384-16
 LOADS SHOWN AT 2.5KW,1.8KW AND 1.5KW
 ON 15A AND 20A BRKRS.
  
 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 SHOWS ALL WIRING TO BE IN CONDUIT.???
 PLEASE VERIFY AND CHANGE IF NESS.
  
 4)NOTE: PLEASE SEE MISSING OUTLETS PER
 210-52 2` OF WALL IN BEDROOMS, 2,3,4.
  
 5)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR A/C EQUIPMENT OUTSIDE. PER 309.1
 OF MECH CODE
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 ETX 8372