Plan Review Notes For Permit 00100482
Permit Number 00100482
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO P.B.COUNTY
 PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY BUILDING DEPT. BEFORE
 PERMIT CAN BE ISSUED.
  
 2)RECORDED COPY OF NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE
 PERMIT CAN BE ISSUED.
  
 3)FLORIDA ENERGY CODE FORMS MUST BE SIGN
 -ED BY OWNER OR AGENT.
  
 4)SURVEY DOES NOT CORRESPOND WITH SITE
 PLAN ON ARCHITECTURAL DRAWINGS. PLEASE
 REVIEW AND CORRECT.
  
 5)THE STAIRS FROM 1ST FLOOR TO 2ND FLOOR
 DO NOT COMPLY WITH CODE.THE SUM OF 2
 RISERS AND A TREAD, EXCLUSIVE OF PROJECT
 -ION OF THE NOSING, IS NOT TO BE LESS
 THAN 24" NOR MORE THAN 25". 97 SBC1007.3
  
 6)DOOR FROM GARAGE TO CONDITIONED AREA
 OF STRUCTURE MUST COMPLY WITH 403.1 OF
 97 FL. ENERGY EFFICIENCY CODE.
  
 7)ENERGY CALULATIONS LIST CONDITIONED
 FLOOR AREA AT 4098 SQFT AND PLANS
 INDICATE 3481 SQFT UNDER AIR. PLEASE
 CLARIFY.
  
 8)PROVIDE MANUAL "J" CALCS FOR ALL 3
 UNITS.
  
 9)PROVIDE POSITIVE AND NEGATIVE WIND
 LOADS FOR OVERHEAD GARAGE DOORS, 3FT
 GARAGE DOOR, FRONT DOOR AND WINDOWS
 ABOVE FRONT DOOR.
  
 10)PROVIDE LITERATURE ON STEEL FLOOR AND
 ROOF SYSTEMS TO BE PUT WITH PLANS FOR
 INSPECTION PURPOSES. INCLUDE SPECIFICAT-
 IONS, FASTENER DETAILS, HEADER CONSTRUCT
 -ION.
  
 11)PLEASE CLARIFY THE ATTACHMENT OF
 STEEL FLOOR JOISTS TO CONCRETE TIE BEAM
 AND STEEL ROOF RAFTERS TO WOOD WALLS.
  
 12)PLEASE CLARIFY METHOD OF ATTACHMENT
 USED TO SECURE DRYWALL TO STEEL ON
 CEILINGS.
  
 13)DETAIL ON SHEET 7 IS NOT CLEAR ON
 ATTACHMENT OF WOOD TRUSSES TO STEEL
 RAFTERS. PLEASE CLARIFY.
  
 14)PLEASE PROVIDE 2COPIES OF DESIGN
 CERTIFICATION COMPLIANCE FORMS. WET
 SIGNATURE, IMPRESSION SEAL AND DATE BY
 DESIGNER OF RECORD IS REQUIRED. SEE
 ATTACHED FORMS.
  
 15)PROVIDE PRODUCT APPROVALS FOR FRONT
 DOOR, 3FT GARAGE DOOR, FIXED GLASS
 WINDOWS AND ARCHED ARCHED WINDOWS.
  
 16)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE THE
 SPECIFIC TYPES OF FASTENERS THAT WILL BE
 USED.
  
 IF YOU HAVE ANY QUESTIONS CALL ROBERT
 MCDOUGAL AT (561)659-8096 EXT.8202