| Plan Review Notes For Permit 00100482 |
| Permit Number |
00100482 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE LIST THE REQ`D BATHS PER | | | 210-52D AND 210-11-C-3. #12 AND 20A | | | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS, | | | YOU SHOW 13.8KW FOR GEN LIGHTING IN | | | LOWER CORNER OF PANEL AND 3.8KW ON | | | PANEL SCHEULE.PLEASE CORRLELATE. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | BOTH MAIN AND PANEL. BOTH MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER | | | 110-9 AND 215-5. | | | | | | 4)NOTE: PLEASE SHOW BLDG STEEL AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM PER | | | 250-50. | | | | | | 5)NOTE: PLEASE SHOW CONDUCTORS FROM | | | METER TO MAIN DISC AND FROM MAIN DISC TO | | | PANEL. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|