| Plan Review Notes For Permit 00100464 |
| Permit Number |
00100464 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1. DUCTS PENETRATING RATED WALLS AT | | | STORAGE ROOM TO HAVE FIRE DAMPERS PER | | | 1997 SMC 610.1.2. LOCATION AND INSTALLA- | | | TION SHALL BE SHOWN ON THE DRAWINGS BY | | | THE DESIGNER PER 1997 SMC 610.6. | | | 2. PROVIDE INFORMATION ON EQUIPMENT TO | | | BE SERVED BY HOOD (FOOD TO BE COOKED, | | | CORE TEMP. OF FOOD, VENT OR EXHAUST REQ- | | | UIREMENTS OF EQUIPMENT, ETC.) | | | 3. NOTE: SEPARATE PERMITS REQUIRED FOR | | | FUEL SYSTEM. SUBMIT 2 SETS OF PLANS | | | ALREADY APPROVED BY DERM AT TIME OF | | | PERMIT APPLICATION FOR THIS WORK. | | | 4. NOTE: SEPARATE PERMITS REQUIRED FOR | | | WALKIN COOLERS/FREEZERS AND HOOD INSTALL | | | ATION. SUBMIT PLANS AT TIME OF PERMIT | | | APPLICATION FOR THESE SYSTEMS PRIOR TO | | | ANY WORK BEING DONE. |
|