Plan Review Notes
Plan Review Notes For Permit 00100464
Permit Number 00100464
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) PLEASE CLEARLY INDICATE FIRE HYDRANT
 LOCATIONS ON OR NEAR THE SITE.
 2) PLEASE CLEARLY INDICATE EMERGENCY
 LIGHT FIXTURE LOCATIONS ON PLANS.
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 4) SERVICE STATION TO COMPLY WITH NFPA
 30A, THE STANDARD FOR AUTOMOTIVE AND
 MARINE SERVICE STATION CODE, AND UNIFORM
 FIRE SAFETY RULES AND STANDARDS,
 CHAPTER 4A-49.
 5) THE UNDERGROUND FUEL TANKS TO COMPLY
 WITH NFPA 30, THE STANDARD FOR THE
 STORAGE AND HANDLING OF COMBUSTIBLE
 LIQUIDS.
 6) PLEASE INDICATE ON THE PLANS, THE
 LENGTHS OF FUEL HOSES PLANNED FOR USE.
 7) PLEASE IDENTIFY TYPE SIGNAGE FOR
 EMERGENCY SHUT-OFF FOR FUEL DISPENSING
 EQUIPMENT.
 8) PLEASE IDENTIFY THE LOCATIONS FOR
 WARNING SIGNS AT THE FUEL DISPENSING
 EQUIPMENT. WHAT WORDING IS PLANNED FOR
 THESE SIGNS.
 9) PLEASE PROVIDE LISTING INFORMATION
 ON DEVICES PLANNED FOR USE AT FUEL
 DISPENSING AREA.