2001-01-08 00:00:00UNSAT, WITH COMMENTS:
 SHEET C2
 ANY WORK PERFORMED OUTSIDE OF SITE
 ALONG THE OKEECHOBEE ROW REQUIRES A DOT
 ROW PERMIT.
 SHEET C-3
 THE DUMPSTER ENCLOSURE MUST HAVE MINIMUM
 OPENINGS OF 12'-6" SO THAT TRASH IS
 ACCESSIBLE TO CITY SANITATION DEPT.
 THERE IS NOT SCALE LISTED ANY WHERE
 VISIBLE PLEASE CLARIFY TYP. ON ALL SHTS.
 SHEET C4
 PLEASE SHOW SILT FENCE AROUND THE
 ENTIRE SITE ASMARKED.
 ADD NOTE TO BALES DETAIL
 NOTE: BALES MUST BE PROVIDED AROUND
 CATCH BASINS AND MANHOLES TO CONTROL
 POLLUTION.
 TOTAL PERVIOUS AND IMPERVIOUS TALLY
 MUST BE LISTED ALONG WITH THE SITE
 TOTAL S.F. AND ACREAGE. AN ADDRESS OR
 PROPERTY CONTROL NUMBER MUST BE STATED.
 THE SITE STORM CHARGES WILL BE CALCULATE
 D FROM THESE NUMBERS.
 DRAINAGE CALCULATIONS MUST BE SUBMITTED
 TO STORM WATER ENGINEER FOR APPROVAL
 JOSE DEL RIOS, STORM WATER DIVISION
 (561) 659 8040.
 I HAVE ATTACHED A STORM REQUIREMENT SHT.
 SHEET C-6
 CITY OF WEST PALM BEACH STANDARD DETAILS
 MUST MUST BE SHOWN ON THIS PLAN. THEY
 MAY BE REQUESTED TO EMAIL
 [email protected]
 SHEET TP-1
 WHERE NEW AND EXISTING SERVICES EXIST.
 PROPOSED LARGE TREES MUST STAY 5'AWAY
 MIN.
 PLEASE IDENTIFY EXISTING METERS AT
 CORNER OF PROPERTY.TO REMAIN?TO BE REM
 OVED? TO BE RELOCATED? OWNER?
 SHOW EXISTING WM WHERE 1" IRRIGATION
 METER SERVICE WILL CONNECTTO AND
 SHOW SIXE AND MATERIAL.
 THE TWO INCH WATER SERVICE IS APPROX.
 320 L.F. TO THE BUILDING, PLEASE VERIFY
 IF THIS REQUIRES A HEALTH DEPARTMENT
 PERMIT.
 NO WATER SERVICE OR DRAINAGE ALLOWED
 IN UNCOVERED DUMPSTER AREAS.REASON:RAIN
 WATER WILL DRAIN INTO SANITARY SYSTEM.
 NEW SANITARY SEWER LINE MUST STAY OUT
 OF RETENTION AREA TO ALLOW MINIMUM
 COVER.
 NO SCALE SHOWN ON THIS SHEET.