| Plan Review Notes For Permit 00100464 |
| Permit Number |
00100464 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. THIS | | | IS REQ`D PER 215-5 AND MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | MIN RATING MAY BE PUT ON PLANS TO COVER | | | UNKNOWN OR CALLS MAY BE PLACED TO FPL | | | FOR AVAILABLE FAULT CURRENT. | | | | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|