2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1]
 PROVIDE SIGNED AND SEALED SURVEYS.
 2]
 ALL NOTES SHALL REFER TO STANDARD BUILD-
 CODE 1997 EDITION,NOT SFBC OR UBC.
 3]
 ADDITIONAL FEES DUE ARE COUNTY IMPACT &
 CITY RADON.
 4]
 NORTH ELEVATION WALL,PROVIDE 2HR WALL
 ASSEMBLY,TABLE 600 REQUIREMENT.
 5]
 REMOVE ANY AND ALL DETAILS THAT DO NOT
 APPLY TO THIS SITE.
 6]
 SUBMIT PRODUCT TEST REPORTS FOR ALL
 EXTERIOR GLAZING ,DOORS AND ROOF COVER.
 7]
 ANY ARCHITECTURAL TRIM ON EXTERIOR IF OF
 WOOD SHALL BE FIRE RETARTANT TREATED,SEE
 F.102.2.7,SBC.
 8]
 PARAPETS SHALL BE CONSTRUCTED OF NON-
 COMBUSTIBLE MATERIAL.
  
  