| 2001-01-08 00:00:00 | 1) EXISTING FIRE SPRINKLER SYSTEM TO | | | REMAIN ACTIVE DURING DEMOLITION, | | | ALTERATION, AND CONSTRUCTION ACTIVITIES. | | | 2) EXISTING FIRE STANDPIPE SYSTEM TO | | | REMAIN ACTIVE DURING DEMOLITION, | | | ALTERATION AND CONSTRUCTION ACTIVITIES. | | | 3) PROVIDE MORE DETAILS ON FUTURE GEN | | | SETS. | | | 4) ENTIRE BUILDING TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED. THIS INCLUDES ALL | | | MECHANICAL, ELECTRICAL AND SERVICE | | | ROOMS. ALSO ALL VERTICAL SHAFTS ARE TO | | | BE SPRINKLER PROTECTED. PLEASE EXPLAIN | | | NEW 5" STANDPIPE ISOLATION VALVES WITH | | | TAMPER SWITCHES. THE PLAN INDICATES THE | | | REMOVAL OF EXISTINMG SPRINKLER SYSTEM | | | PUMP # 2. PLEASE PROVIDE REVISED | | | HYDRAULIC CALCULATIONS. | | | 5) PLEASE PROVIDE COMPLETE FIRE ALARM | | | SYSTEM SHOP DRAWINGS. CUT SHEETS, | | | WIRING DIAGRAM, AND FLOOR PLANS TO | | | BE SUBMITTED UNDER SEPARATE PERMIT. | | | | | | APPROVED PROVISO: | | | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|