| Plan Review Notes For Permit 00100127 |
| Permit Number |
00100127 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD NFPA 101, LIFE SAFETY CODE, 1985 | | | EDITION NOT NFPA 101, LIFE SAFETY CODE, | | | 1997 EDITION. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH FIRE SPRINKLER DRAWING. | | | 3) CLEARLY IDENTIFY INTERIOR FINISH | | | TYPES TO BE USED IN TENANT SPACE. | | | 4) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST, | | | AN AISLE OF AT LEAST 44" WIDE IS | | | PROVIDED AND MAINTAINED, THE DOOR | | | LEADING TO THE STOCKROOM IS NOT | | | SUBJECT TO LOCKING, AND THIS EXIT ONLY | | | PROVIDES NO MORE THAN 50 PERCENT OF | | | EXIT ACCESS IS THROUGH THE STOCKROOM. | | | 5) PLEASE PROVIDE OCCUPANT LOAD DATA | | | FOR TENANT SPACE. |
|