Plan Review Notes
Plan Review Notes For Permit 00100052
Permit Number 00100052
Review Stop R
Sequence Number 3
Notes
Date Text
2001-05-31 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS LAYOUT: ENGINEER TO PROVIDE ALL
 HIS INFORMATION AS REQUIRED BY CHAPTER
 61G15 OF FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
 2-TRUSS ENGINEER TO PROVIDE ORIGINAL
 SIGNATURE ON ALL DRAWINGS AND
 DOCUMENTS SUBMITTED FOR PUBLIC RECORDS
 AS REQUIRED BY CHAPTER 61G15.
 3-TRUSS ENGINEER TO UPDATE ALL GENERAL
 TRUSS DETAILS. SEE COMMENTS ON DWGS.
 4-CLARIFY WHY SIGNATURE ON TRUSS LAYOUT
 IS DIFFERENT FROM SIGNATURE ON THE
 ENGINEERED TRUSSES IF BOTH DOCUMENTS
 ARE SIGNED BY THE SAME ENGINEER.
 5-PROFESSIONAL ENGINEER OF RECORD FOR
 THE STRUCTURE TO REVIEW ALL TRUSS
 DRAWINGS AFTER THEY ARE CORRECTED BY
 THE TRUSS ENGINEER. CHAPTER 61G15.
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
  
  
 NOTE:
 TRUSS ENGINEERED PACKAGE IS GOING TO BE
 RETAINED IN THIS OFFICE TO BE SEND TO
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.