Plan Review Notes
Plan Review Notes For Permit 00100051
Permit Number 00100051
Review Stop P
Sequence Number 2
Notes
Date Text
2001-02-26 00:00:00DENIED;
  
 1.BATHROOM FACILITIES ARE REQUIRED ON
 EACH FLOOR OF SHELL. 94 SPC SEC. 402
 (PUBLIC USE) AND 407.1.4.
 2.AHCA SHOULD BE INVALVED. THIS IS A
 MEDICAL BUILDING.
 3.P3.01 WASTE AND VENT RISER. MAIN VENT
 NOT TIED BACK INTO SANITARY DRAINAGE
 SYSTEM.
 4.FLOOR SINK REQUIRED FOR W/H ON 3RD FL.
 NOT SHOWN ON SANITARY RISER DIAGRAM.
 5.P3.01 FLOOR DRAINS REQUIRED IN 3RD FL.
 BATHROOMS.
 6.FLOOR DRAINS IN BATHROOMS MUST HAVE
 TRAP PRIMERS. TRAP PRIMERS ARE LISTED
 IN PROJECT MANUAL BUT NOT SHOWN ON
 PLANS.
 7.A2.01 2-M.TLC304 AND 303.DOOR SWING
 INFRINGES ON LAVITORYS CLEAR FLOOR
 SPACE. DOORS SHOULD SWING OUT. M AND K
 ALSO INFRINGES ON LAVITORY CLF. FACBC
 4.19.3 AND 4.17.5.
 8.FLUSH VALVES SHALL BE MOUNTED ON THE
 WIDE SIDE OF THE TOILET AREA. FACBC
 4.16.5
 9.P0.01 DELETE GAS CONNECTION DETAIL IF
 NO FUEL GAS WILL BE USED.
 10.P0.01 WATER HEATER DETAIL, CHANGE
 FLOOR DRAIN NOTATIONTO FLOOR SINK.
 11.IF NO MEDICAL GAS WILL BE INSTALLED
 IN SHELL ADD A NOTE TO THAT AFFECT.
 12.P3.01 SHOW LOCATION AND SIZE OF AIR-
 CHAMBER IN ACCORDANCE WITH SPC 607.8.
 2.
 13.FOR ROOF DRAIN CALCULATIONS FOLLOW 94
 SPC CHAPTER 11.ROOF AREA INCLUDES THE
 ROOF AND 1/2 OF THE PARAPET WALL,
 ALSO ROOF OVER MECHANICAL ROOM.PER.
 FIG.1108.4 RAIN IN THIS AREA IS BAST
 ON 4.5 INCHS OF RAIN PER HOUR.
 14.SHOW CHILL WATER SUPPLY LINE ON WATER
 RISER AND LOCATION IN MECH. ROOM.
 15.PARKING GARAGE. SHOW SQ. FT. AREA FOR
 EACH FLOOR DRAIN. SHOW ACCUMULATION
 OF AREA AS PIPES GO FROM 6TH FLOOR TO
 UNDERGROUND. A RISER DIAGRAM WOULD BE
 A GOOD WAY TO ACCOMPLISH THIS.
 16.NO WATER SHOWN IN GARAGE AREA. IS
 THIS TRUE?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377