| 2001-02-26 00:00:00 | DENIED; |
| | |
| | 1.BATHROOM FACILITIES ARE REQUIRED ON |
| | EACH FLOOR OF SHELL. 94 SPC SEC. 402 |
| | (PUBLIC USE) AND 407.1.4. |
| | 2.AHCA SHOULD BE INVALVED. THIS IS A |
| | MEDICAL BUILDING. |
| | 3.P3.01 WASTE AND VENT RISER. MAIN VENT |
| | NOT TIED BACK INTO SANITARY DRAINAGE |
| | SYSTEM. |
| | 4.FLOOR SINK REQUIRED FOR W/H ON 3RD FL. |
| | NOT SHOWN ON SANITARY RISER DIAGRAM. |
| | 5.P3.01 FLOOR DRAINS REQUIRED IN 3RD FL. |
| | BATHROOMS. |
| | 6.FLOOR DRAINS IN BATHROOMS MUST HAVE |
| | TRAP PRIMERS. TRAP PRIMERS ARE LISTED |
| | IN PROJECT MANUAL BUT NOT SHOWN ON |
| | PLANS. |
| | 7.A2.01 2-M.TLC304 AND 303.DOOR SWING |
| | INFRINGES ON LAVITORYS CLEAR FLOOR |
| | SPACE. DOORS SHOULD SWING OUT. M AND K |
| | ALSO INFRINGES ON LAVITORY CLF. FACBC |
| | 4.19.3 AND 4.17.5. |
| | 8.FLUSH VALVES SHALL BE MOUNTED ON THE |
| | WIDE SIDE OF THE TOILET AREA. FACBC |
| | 4.16.5 |
| | 9.P0.01 DELETE GAS CONNECTION DETAIL IF |
| | NO FUEL GAS WILL BE USED. |
| | 10.P0.01 WATER HEATER DETAIL, CHANGE |
| | FLOOR DRAIN NOTATIONTO FLOOR SINK. |
| | 11.IF NO MEDICAL GAS WILL BE INSTALLED |
| | IN SHELL ADD A NOTE TO THAT AFFECT. |
| | 12.P3.01 SHOW LOCATION AND SIZE OF AIR- |
| | CHAMBER IN ACCORDANCE WITH SPC 607.8. |
| | 2. |
| | 13.FOR ROOF DRAIN CALCULATIONS FOLLOW 94 |
| | SPC CHAPTER 11.ROOF AREA INCLUDES THE |
| | ROOF AND 1/2 OF THE PARAPET WALL, |
| | ALSO ROOF OVER MECHANICAL ROOM.PER. |
| | FIG.1108.4 RAIN IN THIS AREA IS BAST |
| | ON 4.5 INCHS OF RAIN PER HOUR. |
| | 14.SHOW CHILL WATER SUPPLY LINE ON WATER |
| | RISER AND LOCATION IN MECH. ROOM. |
| | 15.PARKING GARAGE. SHOW SQ. FT. AREA FOR |
| | EACH FLOOR DRAIN. SHOW ACCUMULATION |
| | OF AREA AS PIPES GO FROM 6TH FLOOR TO |
| | UNDERGROUND. A RISER DIAGRAM WOULD BE |
| | A GOOD WAY TO ACCOMPLISH THIS. |
| | 16.NO WATER SHOWN IN GARAGE AREA. IS |
| | THIS TRUE? |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 659-8096 EXT.8377 |