2001-02-07 00:00:00************DENIED**********************
 1. PLAN SHOWS 3 STORY ATRIUM. SHOW
 COMPLIANCE WITH 1997 SBC 414.4.2 "IN
 ATRIUMS 55FT OR LESS IN HEIGHT WITH A
 VOLUME OF 600,000 CU. FT. OR LESS, A
 SMOKE EXHAUST SYSTEM SHALL BE LOCATED
 AT THE CEILING OF THE ATRIUM. SUCH
 SYSTEMS SHALL EXHAUST 40,000 CFM.
 414.4.3 REQUIRES SUPPLY AIR INLETS
 PROVIDING 75% OF THE EXHAUST. THE
 INLETS MAY BE LOCATED AT THE LOWEST
 LEVEL OF THE ATRIUM.
 2. 414.8 REQUIRES SMOKE CONTROL IN ANY
 OCCUPIED SPACE THAT DOES NOT DIRECTLY
 OPEN INTO THE ATRIUM SHALL BE DESIGNED
 TO PROVIDE NATURAL OR MECHANICAL
 VENTILATION IN ACCORDANCE WITH SMC
 412.5. SHOW COMPLIANCE WITH THIS
 SECTION.
 3. PROVIDE SEQUENCE OF OPERATION FOR
 ATRRIUM SMOKE CONTROL SYSTEM.
 4. ALL SECTIONS OF 1997 SBC 414 THAT
 APPLY TO THIS BUILDING NEED TO HAVE
 COMPLIANCE INDICATED ON THE PLAN FOR
 REVIEW PURPOSES.
 5. PROVIDE DETAIL ON EXHAUST SYSTEM FOR
 THE ATRIUM (EF#5) INCLUDING SHAFT
 PROTECTION AND CFM TO COMPLY WITH NOTE
 1 ABOVE. NOTE PLAN SHOWS FIRE DAMPER AT
 OUTLET .ON M-1.03. IF CODE REQUIRES A
 FIRE DAMPER IN THIS LOCATION IT SHALL
 BE ABLE TO BE OVERRIDDEN FROM A FIRE
 PANEL TO ALLOW THE SMOKE CONTROL SYSTEM
 TO FUNCTION AS REQUIRED BY THE BUILDING
 CODE. PLEASE INDICATE COMPLIANCE WITH
 THIS IN THE SEQUENCE OF OPERATION.
 6. PROVIDE DETAIL FOR MECHANICAL ROOMS
 SHOWING MAUFACTURES REQUIRED CLEARANCE
 AREAS FOR COIL PULL, SERVICE ACCESS,
 ETC. 1997 SMC 304.2 REQUIRES
 ACCESSIBILITY OF ALL EQUIPMENT WITH
 RESPECT TO BUILDING CONSTRUCTION. THE
 NATIONAL ELECTRIC CODE HAS MINIMUM
 REQUIREMENTS WHICH WILL HAVE TO BE
 COMPLIED TO FOR THIS EQUIPMENT. CLEARLY
 SHOW THESE DEDICATED AREAS IN THE
 DETAIL.
 7. PROVIDE INFORMATION ON CONDENSATE
 DRAIN SYSTEM FOR AIR HANDLER EQUIPMENT
 AND OVERFLOW PER 1997 SMC 304.8
 8. PROVIDE INFORMATION FOR VENTILATION
 IN THE MECHANICAL AND MEDICAL GAS
 STORAGEROOMS ON THE FIRST LEVEL PARKING
 GARAGE.