| 2001-02-07 00:00:00 | ************DENIED********************** |
| | 1. PLAN SHOWS 3 STORY ATRIUM. SHOW |
| | COMPLIANCE WITH 1997 SBC 414.4.2 "IN |
| | ATRIUMS 55FT OR LESS IN HEIGHT WITH A |
| | VOLUME OF 600,000 CU. FT. OR LESS, A |
| | SMOKE EXHAUST SYSTEM SHALL BE LOCATED |
| | AT THE CEILING OF THE ATRIUM. SUCH |
| | SYSTEMS SHALL EXHAUST 40,000 CFM. |
| | 414.4.3 REQUIRES SUPPLY AIR INLETS |
| | PROVIDING 75% OF THE EXHAUST. THE |
| | INLETS MAY BE LOCATED AT THE LOWEST |
| | LEVEL OF THE ATRIUM. |
| | 2. 414.8 REQUIRES SMOKE CONTROL IN ANY |
| | OCCUPIED SPACE THAT DOES NOT DIRECTLY |
| | OPEN INTO THE ATRIUM SHALL BE DESIGNED |
| | TO PROVIDE NATURAL OR MECHANICAL |
| | VENTILATION IN ACCORDANCE WITH SMC |
| | 412.5. SHOW COMPLIANCE WITH THIS |
| | SECTION. |
| | 3. PROVIDE SEQUENCE OF OPERATION FOR |
| | ATRRIUM SMOKE CONTROL SYSTEM. |
| | 4. ALL SECTIONS OF 1997 SBC 414 THAT |
| | APPLY TO THIS BUILDING NEED TO HAVE |
| | COMPLIANCE INDICATED ON THE PLAN FOR |
| | REVIEW PURPOSES. |
| | 5. PROVIDE DETAIL ON EXHAUST SYSTEM FOR |
| | THE ATRIUM (EF#5) INCLUDING SHAFT |
| | PROTECTION AND CFM TO COMPLY WITH NOTE |
| | 1 ABOVE. NOTE PLAN SHOWS FIRE DAMPER AT |
| | OUTLET .ON M-1.03. IF CODE REQUIRES A |
| | FIRE DAMPER IN THIS LOCATION IT SHALL |
| | BE ABLE TO BE OVERRIDDEN FROM A FIRE |
| | PANEL TO ALLOW THE SMOKE CONTROL SYSTEM |
| | TO FUNCTION AS REQUIRED BY THE BUILDING |
| | CODE. PLEASE INDICATE COMPLIANCE WITH |
| | THIS IN THE SEQUENCE OF OPERATION. |
| | 6. PROVIDE DETAIL FOR MECHANICAL ROOMS |
| | SHOWING MAUFACTURES REQUIRED CLEARANCE |
| | AREAS FOR COIL PULL, SERVICE ACCESS, |
| | ETC. 1997 SMC 304.2 REQUIRES |
| | ACCESSIBILITY OF ALL EQUIPMENT WITH |
| | RESPECT TO BUILDING CONSTRUCTION. THE |
| | NATIONAL ELECTRIC CODE HAS MINIMUM |
| | REQUIREMENTS WHICH WILL HAVE TO BE |
| | COMPLIED TO FOR THIS EQUIPMENT. CLEARLY |
| | SHOW THESE DEDICATED AREAS IN THE |
| | DETAIL. |
| | 7. PROVIDE INFORMATION ON CONDENSATE |
| | DRAIN SYSTEM FOR AIR HANDLER EQUIPMENT |
| | AND OVERFLOW PER 1997 SMC 304.8 |
| | 8. PROVIDE INFORMATION FOR VENTILATION |
| | IN THE MECHANICAL AND MEDICAL GAS |
| | STORAGEROOMS ON THE FIRST LEVEL PARKING |
| | GARAGE. |