| 2001-02-07 00:00:00 | 1) CODE ANALYSIS BOX ON PAGE G1.01 |
| | INDICATES A ONE HOUR FIRE SEPARATION |
| | BETWEEN THE OFFICE BUILDING AND PARKING |
| | STRUCTURE. PLAN REVIEW COMMENTS |
| | INDICATES A TWO HOUR FIRE SEPARATION. |
| | PLEASE CORRELATE INFORMATION. |
| | 2) PLEASE INDICATE LOCATION OF FIRE |
| | DEPARTMENT CONNECTIONS. THESE DEVICES |
| | ARE TO BE LOCATED NO FARTHER 150 FEET |
| | FROM FIRE HYDRANTS. |
| | 3) ONLY TWO EXITING FIRE HYDRANTS COULD |
| | BE LOCATED ON THE SURVEY. ADDITIONAL |
| | FIRE HYDRANTS APPEAR TO BE NEEDED. ALSO |
| | BE ADVISED THAT THE UTILITIES DEPARTMENT |
| | ARE TO REVIEW THE FIRE SPRINKLER PLANS |
| | AND UNDERGROUND UTILITIES PLANNED FOR |
| | THE SITE. |
| | 4) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | TWO HOUR CONCEALED ROLL-UP SHUTTER AT |
| | DOOR ON PAGE A1.01. |
| | 5) SEPARATE PERMIT REQUIRED FOR MEDICAL |
| | GAS SYSTEMS PLANNED FOR THE BUILDING. |
| | 6) PLEASE EXPLAIN DELUGE FIRE SPRINKLER |
| | SYSTEM PLANNED FOR THE ENTRY SYSTEM ON |
| | PAGE A1.01. |
| | 7) PLEASE PROVIDE MORE DETAILS ON |
| | GENERATOR. |
| | 8) CABLE GUARDS TO COMPLY WITH LIFE |
| | SAFETY CODE REQUIREMENTS. |
| | 9) THE ATRIUM TO COMPLY WITH NFPA 101, |
| | THE LIFE SAFETY CODE, 1985 EDITION, |
| | SECTION 6-2.2.3.5. PLEASE SHOW |
| | COMPLIANCE WITH ALL SECTIONS OF THIS |
| | CODE. PLEASE PROVIDE TETSING CRITERIA |
| | AND EXPECTED PERFORMANCE FOR THE |
| | ATRIUM. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |