Plan Review Notes
Plan Review Notes For Permit 00100051
Permit Number 00100051
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-02-07 00:00:001) CODE ANALYSIS BOX ON PAGE G1.01
 INDICATES A ONE HOUR FIRE SEPARATION
 BETWEEN THE OFFICE BUILDING AND PARKING
 STRUCTURE. PLAN REVIEW COMMENTS
 INDICATES A TWO HOUR FIRE SEPARATION.
 PLEASE CORRELATE INFORMATION.
 2) PLEASE INDICATE LOCATION OF FIRE
 DEPARTMENT CONNECTIONS. THESE DEVICES
 ARE TO BE LOCATED NO FARTHER 150 FEET
 FROM FIRE HYDRANTS.
 3) ONLY TWO EXITING FIRE HYDRANTS COULD
 BE LOCATED ON THE SURVEY. ADDITIONAL
 FIRE HYDRANTS APPEAR TO BE NEEDED. ALSO
 BE ADVISED THAT THE UTILITIES DEPARTMENT
 ARE TO REVIEW THE FIRE SPRINKLER PLANS
 AND UNDERGROUND UTILITIES PLANNED FOR
 THE SITE.
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR
 TWO HOUR CONCEALED ROLL-UP SHUTTER AT
 DOOR ON PAGE A1.01.
 5) SEPARATE PERMIT REQUIRED FOR MEDICAL
 GAS SYSTEMS PLANNED FOR THE BUILDING.
 6) PLEASE EXPLAIN DELUGE FIRE SPRINKLER
 SYSTEM PLANNED FOR THE ENTRY SYSTEM ON
 PAGE A1.01.
 7) PLEASE PROVIDE MORE DETAILS ON
 GENERATOR.
 8) CABLE GUARDS TO COMPLY WITH LIFE
 SAFETY CODE REQUIREMENTS.
 9) THE ATRIUM TO COMPLY WITH NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 6-2.2.3.5. PLEASE SHOW
 COMPLIANCE WITH ALL SECTIONS OF THIS
 CODE. PLEASE PROVIDE TETSING CRITERIA
 AND EXPECTED PERFORMANCE FOR THE
 ATRIUM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910