| Plan Review Notes For Permit 00100051 |
| Permit Number |
00100051 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-14 00:00:00 | ******************UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT A LARGE SCALE | | | DETAIL FOR FIRE PUMP/ AND EQUIPMENT | | | LOCATION. | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | PER 220 AND 215. | | | | | | 3)NOTE: PLEASE NOTE INLINE DISCONNECTS | | | REQ`D FROM GENERATOR TO ATS`S. | | | 225-31/225-32 AND 230-72 FOR GROUPING | | | OF DISC. | | | | | | 4)NOTE: PLEASE SHOW SIZE OF CONDUCTORS | | | AND CONDUITS FROM ATS`S/DISC TO GEN. | | | | | | 5)NOTE:PLEASE SHOW GROUNDING ELECTRODE | | | SYSTE. PLANS SAY TO SEE DETAIL? | | | | | | 6)NOTE: PLEASE PROVIDE CLARIFICATION FOR | | | 695-4-B-1. AND OCP FOR SIZING OF FIRE | | | PUMP. AT 125% | | | | | | 7)NOTE: PLEASE PROVIDE PANEL SCHEDULES | | | SHOWN ON RISER DIAGRAMS IN BOTHSETS OF | | | PLANS. | | | | | | JUST NOTE THAT SHUNT TRIPS ARE | | | NOT RATED FOR MEANS OF DISCONNECTS PER | | | 230-76 AND 230-79 | | | | | | | | | PLEASE SUBMIT CLARIFICATION ON THE ABOVE | | | INFORMATION FOR REVEIW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|