Plan Review Notes
Plan Review Notes For Permit 00100051
Permit Number 00100051
Review Stop E
Sequence Number 2
Notes
Date Text
2001-02-14 00:00:00******************UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT A LARGE SCALE
 DETAIL FOR FIRE PUMP/ AND EQUIPMENT
 LOCATION.
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220 AND 215.
  
 3)NOTE: PLEASE NOTE INLINE DISCONNECTS
 REQ`D FROM GENERATOR TO ATS`S.
 225-31/225-32 AND 230-72 FOR GROUPING
 OF DISC.
  
 4)NOTE: PLEASE SHOW SIZE OF CONDUCTORS
 AND CONDUITS FROM ATS`S/DISC TO GEN.
  
 5)NOTE:PLEASE SHOW GROUNDING ELECTRODE
 SYSTE. PLANS SAY TO SEE DETAIL?
  
 6)NOTE: PLEASE PROVIDE CLARIFICATION FOR
 695-4-B-1. AND OCP FOR SIZING OF FIRE
 PUMP. AT 125%
  
 7)NOTE: PLEASE PROVIDE PANEL SCHEDULES
 SHOWN ON RISER DIAGRAMS IN BOTHSETS OF
 PLANS.
  
 JUST NOTE THAT SHUNT TRIPS ARE
 NOT RATED FOR MEANS OF DISCONNECTS PER
 230-76 AND 230-79
  
  
 PLEASE SUBMIT CLARIFICATION ON THE ABOVE
 INFORMATION FOR REVEIW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372