2001-01-08 00:00:00***********DENIED***********************
 1.MECHANICAL DRAWINGS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ENGINEER OF
 RECORD. SUBMIT SIGNED ANS SEALED PLANS.
  
 2.SHAFTLOCATED BETWEEN ELEVATOR LOBBY
 AND STAIRS HAS SEVERAL DUCTS EXITING.
 ALL DUCTS PENETRATING SHAFT SHALL BE
  
 3.1997 SMC 610.1.2 REQUIRES FIRE DAMPERS
 TO BE LOCATED WHERE DUCTS PENETRATE ALL
 RATED WALLS AND PARTITIONS.
 SMC 610.6 REQUIRES LOCATION AND INSTALL-
 ATION DETAILS TO BE SHOWN AND PROPERLY
 IDENTIFIED ON BUILDINGS BY THE DESIGNER.
  
 4. MECH DUCTS ARE SHOWN RUNNING THROUGH
 ELECTRIC ROOM. NEC DOES NOT PERMIT
  
 5. IDENTIFY AHU CORE AS SHOWN ON M2.01
 LOCATION.
 6. LOCAL AMENDMENTS REQUIRE A MINIMUM OF
 18" CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT STRUCTURE OF EQUIPMENT
 STAND.
  
 7. PROVIDE ELEVATION SHOWING SHAFT AND
 DUCT DETAIL INCLUDING LOCATION OF FIRE
 DAMPERS.
  
 8. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
  
 9. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2