| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE HYDRANTS SHOWN ON SITE PLAN. |
| | PLEASE INDICATE FIRE HYDRANT LOCATIONS |
| | ON SITE PLAN. |
| | 2) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWINGS. BUILDING ADDRESS |
| | TO BE INSTALLED IN ACCORDANCE WITH CITY |
| | CODE REQUIREMENTS. |
| | 3) AN APPLICATION FOR A KNOX-BOX CAN |
| | BE RECEIVED FROM THE FIRE RESCUE |
| | DEPARTMENT. |
| | 4) ELEVATORS TO COMPLY WITH ANSI A.17.1 |
| | AND THE UNIFORM FIRE SAFETY RULES AND |
| | STANDARDS 4A-47. ELEVATORS ARE TO HAVE |
| | BOTH PHASE ONE AND PHASE TWO RECALL |
| | FUNCTIONS. |
| | 5) NO FIRE SPRINKLER SYSTEM DRAWINGS |
| | OR HYDRAULIC CALCULATIONS PROVIDED FOR |
| | OFFICE BUILDING. |
| | 6) NO OCCUPANT LOAD CALCULATIONS |
| | PROVIDED FOR LEASE SPACES. |
| | 7) ADDITIONAL EXIT SIGNAGE IS NEEDED TO |
| | DIRECT PERSONS TO EXIT DOOR LOCATIONS. |
| | 8) MECHANICAL ROOM DOORS (301) WHEN |
| | OPENED BLOCK EXIT DOOR. |
| | 9) STAIRS TO COMPLY WITH NEW STAIRS, |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 10) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, THE LIFE SAFETY CODE, 1985 |
| | EDITION. |
| | 11) PLEASE INDICATE FIRE PROTECTION |
| | DETAILS FOR TOWER BETWEEN PARKING GARAGE |
| | AND OFFICE TOWER. |
| | 12) PLEASE PROVIDE INTERIOR FINISH |
| | INFORMATION FOR EXITS AND OTHER AREAS OF |
| | THE OFFICE BUILDING. |
| | |
| | PARKING GARAGE |
| | 1) NO FIRE SPRINKLER DRAWINGS OR |
| | HYDRAULIC CALCULATIONS PROVIDED WITH |
| | PLANS. |
| | 2) NO FIRE STANDPIPE SYSTEM DRAWINGS |
| | INCLUDED WITH PLANS. |
| | 3) PARKING GARAGE TO COMPLY WITH NFPA |
| | 88, THE STANDARD FOR PARKING STRUCTURES |
| | AND NFPA 101, THE LIFE SAFETY CODE, |
| | 1985 EDITION, SECTION 29.8, PARKING |
| | GARAGES. |
| | 4) THE FIRE SPRINKLER AND FIRE ALARM |
| | SYSTEMS IN BOTH BUILDINGS ARE TO BE |
| | MONITORED BY A LICENSED UL LISTED |
| | CENTRAL STATION APPROVED BY THE FIRE |
| | RESCUE DEPARTMENT. |
| | 5) PLEASE PROVIDE MORE DETAILS ON STEEL |
| | CABLE GUARDRAIL SYSTEM. |
| | 6) CLEARLY IDENTIFY THE REQUIRED TWO |
| | MEANS OF EGRESS FROM EVERY LEVEL OF |
| | THE PARKING GARAGE. |
| | 7) PROVIDE OCCUPANT LOAD CALCULATIONS |
| | FOR THE PARKING GARAGE. |
| | 8) PLEASE PROVIDE INTERIOR FINISH |
| | INFORMATION FOR THE PARKING GARAGE. |