2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLAN REVIEW WAS SUBMITTED FOR
 A 3 STORY OFFICE/MEDICAL BLDG AND GARAGE
 BUT PLANS ONLY REFLECT GARAGE?????
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 , GROUNDING ELECTRODE SYSTEM. ETC.
 215-5
  
 3)NOTE: PLEASE CLARIFY LOADS SHOWN ON
 PANEL SCHEDULES. ONE SHOWS CKT KW THE
 OTHER PHASE KW .?
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS