| Plan Review Notes For Permit 00100039 |
| Permit Number |
00100039 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: NOT ENOUGH ELECTRICAL DETAIL FOR | | | REVIEW. NO BRANCH CIRCUIT SIZES? | | | WHERE ARE CIRCUIT(S) COMING FROM?? | | | WHAT SIZE TRANSFORMER IS BEING INSTALLED | | | ???? LOAD?? | | | IS THERE ONLY LIMITED CIRCUIT(S) COMING | | | IN TO KIOSK? WHERE IS POWER COMING?? | | | KIOSK MUST HAVE CIRCUIT(S) LABELED | | | SHOWING WHERE POWER IS COMING FROM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | 561-659-8096 EXT 8372 | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|