| Plan Review Notes For Permit 00100036 |
| Permit Number |
00100036 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1. 1997 SMC 610 REQUIRES THE LOCATION | | | AND INSTALLATION INSTRUCTIONS FOR EACH | | | REQUIRED FIRE OR FIRE SMOKE DAMPER BE | | | SHOWN AND PROPERLY IDENTIFIED ON THE | | | BUILDING PLANS BY THE DESIGNER. | | | FIRE DAMPERS ARE NOT SHOWN AT THE RATED | | | WALLS FOR THE BATHROOM (159) | | | ARE THE WALL TO THE ELECTRICAL ROOM | | | RATED? | | | ARE THE ELEVATOR LOBBY WALLS FIRE OR | | | SMOKE RATED? | | | INCLUDE ABOVE INFORMATION FOR REVIEW. | | | | | | REVISED PLAN SHOWING LOCATION AND DETAIL | | | OF ABOVE DAMPERS TO BE SUBMITTED AND | | | REVIEWED PRIOR TO THE MECH PERMIT BEING | | | ISSUED |
|