| Plan Review Notes For Permit 00100036 |
| Permit Number |
00100036 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE INDICATE EXIT SIGN LOCATIONS | | | ON PLANS. THEY COULD NOT BE LOCATED | | | WITHIN THE DRAWINGS. | | | 2) NO INTERIOR FINISH NOTES ON PLANS. | | | INTERIOR FINISH IN EXITS TO BE CLASS | | | A OR B. INTERIOR FINISH IN OFFICES TO | | | BE CLASS A,B, OR C. | | | 3) FIRE ALARM NOTES, PAGE FAO.1, | | | INDICATES CLASS B, STYLE C FIRE ALARM | | | CIRCUITS. CLASS A, STYLE D FIRE ALARM | | | CIRCUITS IS ONLY PERMITTED. | | | 4) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | | ON PLANS. CUT SHEETS ON ALL DEVICES | | | PLANNED FOR USE ARE TO BE SUBMITTED. | | | A SEPARATE PLAN AND PERMIT IS REQUIRED. | | | 5) LOCKS ON EXIT DOORS TO COMPLY WITH | | | SPECIAL LOCKING ARRANGEMENTS, SECTION | | | 5-2.1.6, 1985 EDITION OF THE LIFE | | | SAFETY CODE. | | | 6) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. |
|