Plan Review Notes
Plan Review Notes For Permit 00100022
Permit Number 00100022
Review Stop E
Sequence Number 2
Notes
Date Text
2001-02-12 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE PLANS FIRST CAME IN
 WITH MINOR ELECTRICAL WORK BEING DONE
 INONLY LIMITED AREAS. NOW PLANS SHOW
 COMPLETE RE-WIRING OF HOUSE. THE PLANS
 WERE
 ORIGINALLY PASSED WITH A "PROVISO"
 MEANING NOTES WERE ATTACHED AND PLANS
 NEEDED MORE INFORMATION ON THEM BEFORE
 ROUGH INSPECTION. THERE IS NOW ALOT
 MORE WORK SHOWN AND PLANS NEED THE
 FIRST SET OF NOTES ADDRESSED AND NEW
 NOTES FOR OTHER WORKSHOWN.
  
 2)NOTE AS ASKED FOR ON PREVIOUS REVIEW,
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW 2"
 UG CONDUIT GOING TO COTTAGE? OR IS THE
 SERVICE AT THE COTTAGE/GARAGE/APT AND
 GOING TO HOUSE? PLEASE CLARIFY.
  
  
  
  
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 6)NOTE: PLEASE SUBMIT PANEL SCHEDULE/S
 FOR NEW CIRCUITS BEING INSTALLED. 215-5
 PLEASE SHOW PANEL SCHEDULE AT HOUSE/
 MAIN BRKR IS REQ`D IF AT SEPARATE
 STRUCTURE. PER 225-31.
 PLANS SHOW 2POLE 100A GOING TO HOUSE.?
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT8372