Plan Review Notes
Plan Review Notes For Permit 00100022
Permit Number 00100022
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
 ************** PROVISO *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 EQUIPMENT MAINS/PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9
  
 2)NOTE: PLEASE SHOW SERVICE ON COTTAGE
 215-5
  
 3)NOTE: PLEASE NOTE THE REQ`MENT FOR
 BATH(S) RECPETS PER 210-11-C-3
  
 4)NOTE: PLEASE SEE 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 5)NOTE: PLEASE SEE 210-52-C FOR ISLAND
 REC REQ`MENTS.
  
 6)NOTE: MISSING OUTLETS FOR KITCHEN WALL
 SPACE. 210-52
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372