Date Text
2001-01-08 00:00:00CHECKLIST:
 1-NEED TO HAVE AN ACTUAL SURVEY WITH THE
 BUILDING LAYOUT IN ORDER TO ACCURATELY
 REVIEW PLANS FOR TABLE 600 OF SBC 1997
 2-EGRESS WINDOWS ON SECOND FLOOR DON'T
 COMPLY WITH THE MINIMUM REQUIREMENTS
 SECTION 1005.4.4 SBC 1997. MINIMUM
 CLEAR HEIGHT OPENING OF 24" AND MIN.
 TOTAL CLEAR OPENING OF 5.7 SQ. FT.
 3-VERIFY SIZE OF FOOTING. SOIL TEST
 REPORT RECOMMENDS 18" EMBEDMENT OF
 FOOTING. SEE FINDINGS ON PAGE 3 OF 4
 OF SOIL TEST REPORT.
 4-OPTION OF 4080 SLIDING GLASS DOOR DO
 NOT ALLOW 32" MIN. CLEAR OPENING. SEE
 SECTION OF USABLE DOORS OF THE F.H.A.
 5-SOIL TEST REPORT TO BE SIGNED, SEALED
 AND DATED WHEN SUBMITTED FOR PUBLIC
 RECORDS. CHAPTER 471 FLORIDA STATUTES.
 -BORING TESTS SHOW ORGANIC MATERIALS IN
 THE SOIL. REMOVE AS REQUIRED BY SECT'N
 1804.1.8 SBC 1997.
 6-SHOW LOCATION OF VENTS ON ROOF PLAN
 DRAWING BP-3.
 -CLARIFY SIZE OF VENT: 3"X24" OR 6"X24"
 7-SPECIFY SAFETY GLASS AT REQUIRED AREAS
 SEC. 2405.2 SBC 1997. SEE PLANS.
 8-PROVIDE PRODUCT APPROVAL FOR:
 -SLIDING GLASS DOORS, SINGLE HUNG WIND,
 HORIZONTAL SLIDERS.
 -FIREPLACE UL LISTING AND SPECS.
 -TWO HOUR CONCRETE BLOCK: PROVIDE
 CERTIFICATION FROM MANUFACTURER'S
 ENGINEER STATING THAT CONCRETE BLOCK
 EQUIVALENT THICKNESS COMPLIES WITH
 ASTM C140 FOR FIRE RESISTANCE.
 SECTION 709.3 SBC 1997.
 -GARAGE DOORS PRODUCT APPROVALS
 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 ALSO, DRAWING SBC-580-015 DON'T MATCH
 THE REPORT. SEE THE DATE OF DRAWING.
 9-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 COMMENTS ON FORM SUBMITTED.
 10:ENERGY CALCULATIONS:
 -COMPLETE TOP FORM.
 -SEE COMMENTS ON EACH FORM.
 -WILL NEED ORIGINAL ENERGY CALCULATIONS
 FOR EACH ADDRESS WITH ORIGINAL
 SIGNATURES.
 11-PROVIDE CONSTRUCTION DRAWINGS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURES
 OR CLARIFY IF IT'S GOING TO BE UNDER
 A SEPARATE CONTRACT.
 12-SPECIFY FIREBLOCKING AS REQUIRED.
 SEE PLANS FOR COMMENTS.SEC 2305 SBC/97
 13-BATHROOM TYPE "B" WAS SELECTED TO
 COMPLY WITH THE FAIR HOUSING ACT, ALL
 OTHER BATHROOMS STILL NEED TO COMPLY
 WITH THE F.H.A. REQUIREMENTS EXCEPT
 FOR MANEUVERING AND CLEAR FLOOR SPACES
 14-PROVIDE 1 1/2" WATER STOP AT MASONRY
 WALL. SEC 2111.6 CITY AMENDMENTS.
 15-STORM PANELS:
 -PROVIDE COMPLETE INSTALLATION SCHEDULE
 AS PER SAMPLE ATTACHED AND KEY PLAN.
 -SPECIFY/HIGHLIGHT SPECIFIC MOUNTING
 CONDITIONS AND AND ANCHORS TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO.
 16-SEE COMMENTS ON PLANS FOR ADDITIONAL
 COMMENTS.
  
  
  
 NOTES:
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.
 -PLEASE RETURN REVIEWED SET AFTER THE
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.