Plan Review Notes
Plan Review Notes For Permit 00091533
Permit Number 00091533
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SHT.SH-1-GENERAL NOTE #6-THE PLUMBING
 CODE IN EFFECT IS THE 1994 EDITION OF
 THE STANDARD PLUMBING CODE.REVISE NOTE.
  
 2)MODELS "A","B"&"BR"DO NOT COMPLY W/THE
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205,
 REQUIREMENT #7(2)(B)
 A)A 30"X 48" MANEUVERING SPACE IS REQD.
 OUTSIDE OF THE DOOR SWING.
 B)FLOOR PLAN SHOWS DOOR SWINGING INTO
 BATHROOM AND 1/4"PLAN SHOWS DOOR SWING-
 ING OUT.CHECK ALL LAYOUTS AND COMPLY W/
 FHA.
 C)WATER CLOSETS SHALL BE LOCATED 1'-6"
 FROM WALL.
 D)A MIN.OF 40"IS REQD.BETWEEN ALL
 OPPOSING BASE CABINETS,COUNTERTOPS,
 APPLIANCES AND WALLS.CLEARLY SHOW AT
 ENTRY.
  
 3)SUBMIT DETAILS OF REINFORCEMENT FOR
 FUTURE GRAB BARS.COMPLY W/FHA 24 CFR
 100.205 REQ.#6.SEE FIGS.#3,4,5.
  
 4)SUBMIT WATER RISERS FOR EACH UNIT.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 IF YOU HAVE QUESTIONS CALL:
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER
 561-659-8096,EXR.8377.