| Plan Review Notes For Permit 00091533 |
| Permit Number |
00091533 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SHT.SH-1-GENERAL NOTE #6-THE PLUMBING | | | CODE IN EFFECT IS THE 1994 EDITION OF | | | THE STANDARD PLUMBING CODE.REVISE NOTE. | | | | | | 2)MODELS "A","B"&"BR"DO NOT COMPLY W/THE | | | FEDERAL FAIR HOUSING ACT 24 CFR 100.205, | | | REQUIREMENT #7(2)(B) | | | A)A 30"X 48" MANEUVERING SPACE IS REQD. | | | OUTSIDE OF THE DOOR SWING. | | | B)FLOOR PLAN SHOWS DOOR SWINGING INTO | | | BATHROOM AND 1/4"PLAN SHOWS DOOR SWING- | | | ING OUT.CHECK ALL LAYOUTS AND COMPLY W/ | | | FHA. | | | C)WATER CLOSETS SHALL BE LOCATED 1'-6" | | | FROM WALL. | | | D)A MIN.OF 40"IS REQD.BETWEEN ALL | | | OPPOSING BASE CABINETS,COUNTERTOPS, | | | APPLIANCES AND WALLS.CLEARLY SHOW AT | | | ENTRY. | | | | | | 3)SUBMIT DETAILS OF REINFORCEMENT FOR | | | FUTURE GRAB BARS.COMPLY W/FHA 24 CFR | | | 100.205 REQ.#6.SEE FIGS.#3,4,5. | | | | | | 4)SUBMIT WATER RISERS FOR EACH UNIT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | IF YOU HAVE QUESTIONS CALL: | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER | | | 561-659-8096,EXR.8377. |
|