Plan Review Notes For Permit 00091533
Permit Number 00091533
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00NOTES;
 1.ALL MASTER BEDROOM SUITES [BEDROOM,
 BATHROOM, AND CLOSET] THAT HAVE
 300CFM'S OR MORE REQUIRE A RETURN
 AIR DUCT OR RELIEF VENT OR GRILL
 FROM BEDROOM.
 2.[ NOTE 1 ON MP-4 PAGES] ADD R-6
 ROUND DUCT AS AN EXCEPTABLE DUCT
 MATERIAL.
 3."B" MODELS RETURN AIR SHOULD BE FROM
 HALLWAY NOT LAUNDRY ROOM.
 4.ALL MASTER BATHROOMS WITH A DOOR ON
 TOILET ROOM MUST ALSO HAVE AN EXHAUST
 FAN IN TUB OR TOILET ROOM PER 503.3.1