| Plan Review Notes For Permit 00091518 |
| Permit Number |
00091518 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------ | | | 2ND REVIEW | | | | | | 1] SHALL SUBMIT RECORDED NOTICE OF | | | COMMENCEMENT BEFORE PERMIT ISSUE. | | | 2] PLEASE USE BLANK WALL SECTION DETAIL | | | PROVIDED, FILL IN INFORMATION THAT | | | WILL BE USED FOR YOUR PROJECT. | | | 3] DOOR REPORT PROVIDED IS EXPIRED, | | | SUBMIT CURRENT REPORT. | | | 4] SPECIFY HORIZONAL DISTANCE BETWEEN | | | WATERS EDGE OF POOL AND NEW WINDOWS. | | | 5] WINDOW REPORT DOES NOT ALLOW FOR 5' | | | HORIZONAL WIDTH [SEE MAXIMUM SPAN | | | CHART] ALSO, PLEASE PROVIDE WINDOW | | | BUCK ATTACHMENT DETAIL. | | | 6] PLEASE ADDRESS IMPACT PROTECTION FOR | | | NEW WINDOWS. | | | 7] NEW WALLS SHALL HAVE PROPERLY SPACED | | | RECEPTACLES, ALL EXTERIOR DOORS SHALL | | | BE PROVIDED WITH A LIGHTING FIXTURE. | | | 8] VERIFY IF NEW SPACE WILL BE AIR- | | | CONDITIONED. | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096 | | | EXT: 8456 |
|