| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT A FIRST FLOOR PLAN SHOWING ALL | | | NEW PLUMBING TO BE INSTALLED.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 2)DRY VENTS NOT PERMITTED PER SPC SEC. | | | 906.2.1. | | | | | | 3)SHOW LXW OF SHOWERS.COMPLY W/COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.409.8.2. | | | | | | 4)SUBMIT SANITARY RISER DIAGRAMS FOR ALL | | | AREAS WHERE NEW PLUMBING WILL BE IN- | | | STALLED.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | 5)A TRAP IS REQD.ON THE DRIP DRY PER | | | SPC SEC.401.4. | | | | | | 6)SANITARY RISERS SHALL CORRELATE W/ | | | FLOOR PLAN.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | CALL IF YOU HAVE QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|