Plan Review Notes
Plan Review Notes For Permit 00091487
Permit Number 00091487
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT A FIRST FLOOR PLAN SHOWING ALL
 NEW PLUMBING TO BE INSTALLED.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 2)DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.
  
 3)SHOW LXW OF SHOWERS.COMPLY W/COUNTY-
 WIDE AMENDMENTS TO SPC SEC.409.8.2.
  
 4)SUBMIT SANITARY RISER DIAGRAMS FOR ALL
 AREAS WHERE NEW PLUMBING WILL BE IN-
 STALLED.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 5)A TRAP IS REQD.ON THE DRIP DRY PER
 SPC SEC.401.4.
  
 6)SANITARY RISERS SHALL CORRELATE W/
 FLOOR PLAN.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.