| Plan Review Notes For Permit 00091487 |
| Permit Number |
00091487 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT MORE INFORMATION | | | ON PANEL SCHEDULES, LOAD CALAULATIONS | | | PANEL FOR GREAT ROOM SHOWN ??? IS THIS | | | EXISTING? THE NEW RISER SHOWS DOCK PANEL | | | IS IT MAIN BRKR? WHERE IS ACTIVITY BLDG? | | | SEPARATE STRUCTURE REQ`S MAIN. | | | PLEASE SHOW ALL ELECTRICAL PANEL LOCAT- | | | -IONS ON PLANS. | | | | | | 2)NOTE: PLEASE NOTE THAT MORE THAN 50% | | | OF BLDG IS BEING DONE.SMOKE DETECTORS | | | ARE GOING TO BE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT BEING INSTALLED. MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER | | | 110-9 215-5. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | OR IF A MEETING IS NEEDED PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT8372 |
|