Plan Review Notes
Plan Review Notes For Permit 00091478
Permit Number 00091478
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) SMOKE DETECTORS TO BE INSTALLED NO
 CLOSER THAN THREE FEET TO ANY AIR
 CONDITIONER DIFFUSER.
 2) SMOKE DETECTOR REQUIRED ABOVE MAIN
 FIRE ALARM CONTROL PANEL.
 3) HORN STROBES ARE TO BE MOUNTED NOT
 LESS THAN 80 INCHES AND NO HIGHER THAN
 96 INCHES FROM THE FLOOR.
 4) MANUAL PULL STATIONS SHALL BE
 INSTALLED NOT LESS THAN 3 1/2 FEET AND
 NO MORE THAN 4 1/2 ABOVE THE FLOOR.
 5) SYSTEM SUBJECT TO INSPECTION BY FIRE
 RESCUE PERSONNEL.