| Plan Review Notes For Permit 00091478 |
| Permit Number |
00091478 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS TO BE INSTALLED NO | | | CLOSER THAN THREE FEET TO ANY AIR | | | CONDITIONER DIFFUSER. | | | 2) SMOKE DETECTOR REQUIRED ABOVE MAIN | | | FIRE ALARM CONTROL PANEL. | | | 3) HORN STROBES ARE TO BE MOUNTED NOT | | | LESS THAN 80 INCHES AND NO HIGHER THAN | | | 96 INCHES FROM THE FLOOR. | | | 4) MANUAL PULL STATIONS SHALL BE | | | INSTALLED NOT LESS THAN 3 1/2 FEET AND | | | NO MORE THAN 4 1/2 ABOVE THE FLOOR. | | | 5) SYSTEM SUBJECT TO INSPECTION BY FIRE | | | RESCUE PERSONNEL. |
|