| Plan Review Notes For Permit 00091446 |
| Permit Number |
00091446 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-05-22 00:00:00 | ******************PROVISO*************** | | | | | | DRAWING M2.1 - THIS SPACE IS NO LONGER | | | APARTMENS BUT BEING UTILIZED AS OFFICE | | | SPACE,LINE 14 INDICATES A WALL WITH | | | TO SETS OF DOUBLE DOORS GOING TO | | | ELEVATORS.IS THIS WALL A RATED WALL | | | FOR TENANT SEPARATION?(FIRE DAMPER | | | FOR DUCT PENETRATION.) | | | | | | AIR COOLED SPLIT SYSTEM SCHEDULE ON | | | DRAWING M5.1 REFLECTS THREE SANYO SPILT | | | SYSTEMS (1-1 THRU 1-3), BUT SUBMITTAL | | | DATA FOR UNITS 1-1 & 1-2 ARE SANYO | | | WHERE AS 1-3 IS FIRST CO.PLANS AND | | | NEED TO REFLECT THAT OF THE SUBMITTAL | | | DATA. | | | | | | DRAWING M4.1 DETAIL NEEDS TO REFLECT | | | REFRIGERANT LINES GOING TO CONDENSERS | | | ON THE ROOF INSTEAD OF GARAGE. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|