Plan Review Notes
Plan Review Notes For Permit 00091385
Permit Number 00091385
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 2)LOUNGE SINK SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.CLEARLY SHOW COMPLIANCE ON
 PLANS.
  
 3)SHT.A-5-DETAIL #A/6-H.C.LAVATORY SHALL
 COMPLY W/FACBC SEC.4.19.2.(MIN.29"TO
 BOTTOM OF APRON AND MAX.34"TO RIM.)
  
 4)SUBMIT MANUF.SHEETS/VENDOR DRAWINGS
 FOR R/O SYSTEM.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 5)SUBMIT UPDATED U.L.ASSEMBLY DETAIL/#
 FOR PIPE PENETRATION DETAIL ON P-1.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4
  
 6)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC 501.7.IF HEATER IS ELEVATED
 SUPPLY SHIP'S LADDER W/PLATFORM OR
 RELOCATE HEATER TO FLOOR.
  
 7)VACUUM RELIEF VALVE SHALL BE INSTALLED
 PER MANUF.RECOMMENDATIONS AND IN
 COMPLIANCE W/ANSI Z21.22.SPC SEC.507.1.2
  
 8)DRY VENTS ARE NOT PERMITTED PER SPC
 SEC.906.2.1.(SEE WATER CLOSETS.)
  
 9)WATER CLOSETS NOT PERMITTED ON HORIZ.
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.TWO WATER CLOSETS MAY BE
 VENTED PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 10)INDICATE SIZE OF PVC SLEEVE FOR
 CONCENTRATE PIPING.SLEEVE SHALL BE LARGE
 ENOUGH FOR REMOVAL/REPLACEMENT OF PIPING
 PER SPC SEC.601.7.
  
 11)BFP DEVICE SHALL BE RPZ TYPE.RELIEF
 VALVE SHALL BE PIPED TO APPROVED POINT
 OF DISPOSAL.SPC 606.4.1.
  
 12)ROOM 103-(H.C.TOILET ROOM)-WHEELCHAIR
 TURNING DIAMETER SHALL BE A CLEAR SPACE
 OF 60".(PLAN SHOWS INFRINGEMENT OF W.C.
 AND DOOR OPENING.)FACBC SEC.4.2.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.