| 2001-01-08 00:00:00 | 1)DRINKING FOUNTAIN SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE |
| | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING |
| | OR STOOPING. |
| | |
| | 2)LOUNGE SINK SHALL COMPLY W/FACBC SEC. |
| | 4.24.1-4.24.7.CLEARLY SHOW COMPLIANCE ON |
| | PLANS. |
| | |
| | 3)SHT.A-5-DETAIL #A/6-H.C.LAVATORY SHALL |
| | COMPLY W/FACBC SEC.4.19.2.(MIN.29"TO |
| | BOTTOM OF APRON AND MAX.34"TO RIM.) |
| | |
| | 4)SUBMIT MANUF.SHEETS/VENDOR DRAWINGS |
| | FOR R/O SYSTEM.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |
| | |
| | 5)SUBMIT UPDATED U.L.ASSEMBLY DETAIL/# |
| | FOR PIPE PENETRATION DETAIL ON P-1. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.4 |
| | |
| | 6)WATER HEATER SHALL BE READILY ACCESS- |
| | IBLE PER SPC 501.7.IF HEATER IS ELEVATED |
| | SUPPLY SHIP'S LADDER W/PLATFORM OR |
| | RELOCATE HEATER TO FLOOR. |
| | |
| | 7)VACUUM RELIEF VALVE SHALL BE INSTALLED |
| | PER MANUF.RECOMMENDATIONS AND IN |
| | COMPLIANCE W/ANSI Z21.22.SPC SEC.507.1.2 |
| | |
| | 8)DRY VENTS ARE NOT PERMITTED PER SPC |
| | SEC.906.2.1.(SEE WATER CLOSETS.) |
| | |
| | 9)WATER CLOSETS NOT PERMITTED ON HORIZ. |
| | WET VENTS PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.911.1.1.TWO WATER CLOSETS MAY BE |
| | VENTED PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.911.1.3. |
| | |
| | 10)INDICATE SIZE OF PVC SLEEVE FOR |
| | CONCENTRATE PIPING.SLEEVE SHALL BE LARGE |
| | ENOUGH FOR REMOVAL/REPLACEMENT OF PIPING |
| | PER SPC SEC.601.7. |
| | |
| | 11)BFP DEVICE SHALL BE RPZ TYPE.RELIEF |
| | VALVE SHALL BE PIPED TO APPROVED POINT |
| | OF DISPOSAL.SPC 606.4.1. |
| | |
| | 12)ROOM 103-(H.C.TOILET ROOM)-WHEELCHAIR |
| | TURNING DIAMETER SHALL BE A CLEAR SPACE |
| | OF 60".(PLAN SHOWS INFRINGEMENT OF W.C. |
| | AND DOOR OPENING.)FACBC SEC.4.2.3. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | QUESTIONS. |