Plan Review Notes
Plan Review Notes For Permit 00091385
Permit Number 00091385
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVIDE INFORMATION ON EF-2 OPERATION
 AND WHERE MAKE UP AIR FOR THIS FAN IS
 OBTAINED FROM. 2000CFM ON TOP OF THE CFM
 FROM THE BATH EXHAUST FANS FAR EXCEED
 THE AMOUNT OF OUTSIDE AIR PROVIDE TO THE
 SPACE FOR AIR BALANCE
 NOTE: DUCT SMOKE DETECTORS TO BE TIED TO
 BLDG FIRE ALARM OR HORN AND STROBE FOR
 NOTIFICATION PER NFPA 90A 4-4.4