| Plan Review Notes For Permit 00091385 |
| Permit Number |
00091385 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVIDE INFORMATION ON EF-2 OPERATION | | | AND WHERE MAKE UP AIR FOR THIS FAN IS | | | OBTAINED FROM. 2000CFM ON TOP OF THE CFM | | | FROM THE BATH EXHAUST FANS FAR EXCEED | | | THE AMOUNT OF OUTSIDE AIR PROVIDE TO THE | | | SPACE FOR AIR BALANCE | | | NOTE: DUCT SMOKE DETECTORS TO BE TIED TO | | | BLDG FIRE ALARM OR HORN AND STROBE FOR | | | NOTIFICATION PER NFPA 90A 4-4.4 |
|