| Plan Review Notes For Permit 00091378 |
| Permit Number |
00091378 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE INTERIOR FINISH | | | INFORMATION FOR SPACE. | | | 2) PLEASE PROVIDE MORE INFORMATION ON | | | ONE AND TWO HOUR FIRE SHUTTERS PLANNED | | | FOR USE. | | | 3) PLEASE INDICATE WHAT TYPE OF STORAGE | | | IS PLANNED FOR THE WAREHOUSE. | | | 4) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR THE SPACE. | | | 5) PLEASE PROVIDE MORE DETAILS FOR | | | CANOPY | | | 6) STAIRS TO COMPLY WITH NEW STAIR | | | REQUIREMENTS FROM NFPA 101, THE LIFE | | | SAFETY CODE, 1985 EDITION. | | | 7) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMIT FOR THE INSTALLATION OF THE | | | FIRE ALARM SYSTEM SHOWN IN DRAWINGS. | | | 8) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | | EDITION. | | | 9) ALL STORAGE ROOMS ARE TO BE SEPARATED | | | BY AT LEAST ONE HOUR FROM OTHER SPACES | | | SINCE NO FIRE SPRINKLERS ARE PRESENT. |
|