| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE PLANS NEED TO SHOW | | | ALL BRANCH CIRCUIT #`S AND CORRELATE | | | WITH SUBMITTED PANEL SCHEDULES. | | | | | | 2)NOTE: PLEASE NOTE PLANS MISSING BLDG. | | | STEEL PER 250-50. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4)NOTE: PLEASE NOTE THAT BOTH PANELS ARE | | | SHOWN AS PANELS "LP"??? PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE NOTE THAT PLANS ONLY SHOW | | | LOCATION OF ONE PANEL?? PLEASE SHOW BOTH | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|