Plan Review Notes
Plan Review Notes For Permit 00091295
Permit Number 00091295
Review Stop E
Sequence Number 5
Notes
Date Text
2001-09-10 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO SHOW
 ALL BRANCH CIRCUIT #`S AND CORRELATE
 WITH SUBMITTED PANEL SCHEDULES.
  
 2)NOTE: PLEASE NOTE PLANS MISSING BLDG.
 STEEL PER 250-50.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE THAT BOTH PANELS ARE
 SHOWN AS PANELS "LP"??? PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE THAT PLANS ONLY SHOW
 LOCATION OF ONE PANEL?? PLEASE SHOW BOTH
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372