Plan Review Notes
Plan Review Notes For Permit 00091295
Permit Number 00091295
Review Stop P
Sequence Number 2
Notes
Date Text
2001-02-27 00:00:00DENIED;
  
 1.BATHROOM FACILITIES ARE REQUIRED IN
 MANUFACTURING AREA. SUBMIT INFORMATION
 SHOWING NUMBER OF EMPLOYEES PER SHIFT
 AND INDICATE LIGHT OR HEAVY MANUFACT-
 URING.
  
 2.PAGE M-1 NOTE 8;
 A. FLOOR DRAINS ARE NOT SHOWN ON
 SANITARY RISER DIAGRAM.
 B.SPECIFY TYPE OF AIR ARRESTERS TO
 BE USED. AIR ARRESTERS MUST BE
 ASSESIBLE 607.8.2 AND 607.8.3.
  
 3.SINK IN BREAK ROOM; SHOW ARCHITECTAL
 DRAWING MEETING ALL REQUIREMENTS OF
 97 FACBC SEC. 4.24.1 THRU 4.24.7.
  
 4. PLUMBING RISER NOT CORRECT.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377