| Plan Review Notes For Permit 00091295 |
| Permit Number |
00091295 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-27 00:00:00 | *****************DENIED***************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | PROVIDE EQUIPMENT INFORMATION, DUCT | | | LAYOUT, AIR BALANCE, FRESH AIR | | | CALCULATIONS AND EXHAUST FAN | | | SPECIFICATIONS. | | | | | | SUBMIT PLANS WITH MECHANICAL PERMIT | | | APPLICATION PRIOR TO START OF ANY | | | MECHANICAL WORK BEING DONE. | | | | | | NOTE:IF ABOVE CEILING IS RETURN PLENUM | | | THERE SHALL BE NO COMBUSTIBLES IN | | | THIS SPACE AS PER 97 SMC 609.1.1. | | | | | | REFERENCE DRAWING M-1, HVAC NOTES | | | #5 - EMERGENCY PAN MUST HAVE A | | | FLOAT SWITCH AS PER 97 SMC | | | 304.8.6.1. |
|