Plan Review Notes
Plan Review Notes For Permit 00091295
Permit Number 00091295
Review Stop B
Sequence Number 2
Notes
Date Text
2001-02-26 00:00:00PERMIT # 00091295
 4700 GEORGIA AV.
 OVERLAND CONSTRUCTION
 PHONE 683-3210
  
 1)- NOTICE OF COMMENCEMENT: OWNER NAME
 ON PROPERTY APPRAISER IS DANIEL M FOWLER
 ON THE PERMIT APPLICATION LISTED AS
 FOWLER SHEET METAL, INC. THE BUILDING
 DEPARTMENT WILL NEED TO SEE PROOF OF
 CHANGE OF OWNERSHIP OR THE PERMIT APPLI-
 CATION WILL NEED TO BE CHANGED, BOTH THE
 NOTICE OF COMMENCEMENT & THE PROPERTY
 APPRAISERS SCREEN MUST AGREE.
  
 2)- SHEET A-5 DETAIL 4/A-5 EXISTING
 BUILDING (LOT 61-64) SOUTH WALL OF NEW
 BUILDING IS A PROPERTYLINE WALL. THE
 OVERHANG AND GUTTER CANNOT OVERHANG THE
 PROPERTYLINE WALL, NOR CAN THE EXISTING
 BUILDING BE JOINED, UNDER DIFFERENT
 QWNERSHIP & PROPERTY CONTROL NUMBER.
 THE SOUTH WALL WILL REQUIRE A MINIMUM OF
 A 3HR. WALL. TABLE 709.3.1 THE MINIMUM
 EQUIVALENT THICKNESS FOR LIMESTONE
 MASONARY WALLS IS A 5.0. SHOW COMPLIANCE
 FIRE RATINGS MUST BE TAKEN FROM BOTH
 SIDES OF THE WALL WHEN THE EXTERIOR
 BUILDING WALL IS 5'-0" OR LESS IN HORI-
 ZONTAL SEPERATION.NO OPENINGS.
  
 3)- SHEET A-5 SECTION 3: (EAST WALL)
 THIS WALL WILL ALSO REQUIRE A 3 HR. WALL
 SHOW COMPLIANCE THE EQUIVALENT THICKNESS
 FOR LIMESTONE MASONARY WALL (MINIMUM) IS
 5.0 TABLE 709.3.1.
  
 JIM WITMER
 BUILDING PLAN REVIEW