| Plan Review Notes For Permit 00091295 |
| Permit Number |
00091295 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-02-02 00:00:00 | INSUFFICIENT INFORMATION FOR | | | MECHANICAL REVIEW. | | | | | | PROVIDE EQUIPMENT SPECIFICATION, AIR | | | BALANCE SCHEDULES, EXHAUST FAN | | | SPECIFACTIONS WITH MECHANICAL PERMIT | | | APPLICATION. | | | | | | IF ABOVE CEILING IS RETURN PLENUM, | | | THERE SHALL BE NO COMBUSTIBLES IN THIS | | | SPACE AS PER 1997 SMC 609.1.1. | | | | | | REFERENCE DRAWING M-1, HVAC NOTES, #5 | | | 2" EMERGENCY PAN MUST HAVE A FLOAT | | | SWITCH AS PER 1997 SMC 304.8.6.1. |
|