Plan Review Notes
Plan Review Notes For Permit 00091251
Permit Number 00091251
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1. SHAFT ENCLOSURE REQUIRES MIN. 6"
 CLEARANCE BETWEEN DUCT AND INSIDE OF
 SHAFT OR APPROVED FIRE BLANKET PER NFPA
 96
 2. FIRE SUPPRESSION SYSTEM REQUIRES
 ADDITIONAL PERMIT SUBMIT PLANS AT TIME
 OF PERMIT APPLICATION.