| Plan Review Notes For Permit 00091238 |
| Permit Number |
00091238 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | STORAGE ROOMS ARE TO BE AT LEAST ONE | | | HOUR FIRE SEPARATED FROM OTHER PORTIONS | | | OF THE BUILDING. THE CODE FOR BUSINESS | | | OCCUPANCIES INDICATES "ANY AREA USED FOR | | | GENERAL STORAGE, BOILER, OR FURNACE | | | ROOMS, FUEL STORAGE, JANITOR CLOSETS, | | | MAINTENANCE SHOPS, INCLUDING WOODWORKING | | | AND PAINTING AREAS, AND KITCHENS SHALL | | | BE SEPARATED FROM OTHER PARTS OF THE | | | BUILDING BY CONSTRUCTION HAVING A | | | FIRE RESISTANCE RATING OF NOT LESS THAN | | | 1 HOUR, AND ALL OPENINGS SHALL BE | | | PROTECTED WITH SELF-CLOSING FIRE DOORS". | | | "EXCEPTION: AREAS PROTECTED BY AN | | | AUTOMATIC EXTINGUISHING SYSTEM". | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|