| Plan Review Notes For Permit 00091238 |
| Permit Number |
00091238 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED. (RETURN AIR PLENUM SPACE ABOVE | | | CEILING IS COMMON AREA FOR ALL AREAS | | | AND UNITS. | | | CONNECT TO BUILDING FIRE ALARM PER NFPA | | | 92A 4-4.4.2 OR HORN AND STROBE PER | | | 4-4.4.3 |
|