| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT SIGNED,DATED AND SEALED WATER |
| | AND SANITARY RISER DIAGRAMS FOR REVIEW. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | 2)EACH PUBLIC AND COMMON USE TOILET ROOM |
| | SHALL COMPLY W/FACBC SEC.4.22. |
| | |
| | 3)SUBMIT OCCUPANT LOAD BASED ON |
| | HABITABLE FLOOR SPACE PER TABLE 407 OF |
| | THE SPC.SEE SPC SEC.407.1.3.FOR ALLOWED |
| | DEDUCTIBLE AREAS. |
| | |
| | 4)DOORS TO ACCESSIBLE TOILET ROOMS SHALL |
| | COMPLY W/FACBC SEC.4.13.DOORS SHALL NOT |
| | SWING INTO THE CLEAR FLOOR SPACE REQD. |
| | FOR ANY FIXTURE.FACBC SEC.4.22.2. |
| | |
| | 5)FLOOR DRAINS W/TRAP PRIMERS ARE REQD. |
| | IN ALL TOILET ROOMS PER SPC SEC.409.4.1. |
| | |
| | 6)SINK IN STAFF LOUNGE SHALL COMPLY W/ |
| | FACBC SECS.4.24.1-4.24.7. |
| | |
| | 7)CLEARLY SHOW REQD.WHEELCHAIR TURNING |
| | SPACE IN ALL TOILET ROOMS PER FACBC SEC. |
| | 4.2.3. |
| | |
| | 8)A MIN.OF 1 DRINKING FOUNTAIN IS REQD. |
| | PER SPC TABLE 407.BOTTLED WATER IS NOT |
| | AN ACCEPTED SUBSTITUTE FOR THE D.F. |
| | PROVISIONS SHALL BE MADE FOR PEOPLE WHO |
| | HAVE TROUBLE BENDING OR STOOPING PER |
| | FACBC SEC.4.1.3(10)(A). |
| | |
| | 9)WALLS IN TOILET ROOMS SHALL BE NON- |
| | ABSORBENT TO A HEIGHT OF 4'PER SBC SEC. |
| | 1204.2. |
| | |
| | 10)WATER HEATER SHALL BE READILY ACCESS- |
| | IBLE PER SPC SEC.501.7. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |