| Plan Review Notes For Permit 00091238 |
| Permit Number |
00091238 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1. CONFLICT BETWEEN M-1 AND A-1.0 ON | | | EQUIPMENT TYPE | | | 2. MECH DRAWINGS NOT SIGNED AND SEALED. | | | 3. NO INFORMATION ON DUCT SMOKE DETECTOR | | | OR FAN SHUT DOWN | | | 4. EXHAUST AIR FANS TO RUN WHEN BUILDING | | | IS OCCUPIED TO COMPLY WITH 1997 SMC | | | 501.2 (AIR BALANCE) NOT OPERATED BY WALL | | | SWITCH. | | | 5. ANY PIPING RELATED TO MEDICAL EQUIP- | | | MENT SHALL COMPLY WITH NFPA 99C AND | | | REQUIRES MECHANICAL PERMIT. PROVIDE | | | DETAILED PLANS FOR WORK SHOWING CODE | | | COMPLIANCE PRIOR TO COMENCEMENT OF WORK. |
|