| Plan Review Notes For Permit 00091238 |
| Permit Number |
00091238 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISHES IN EXITS SHALL BE | | | CLASS A OR B IN EXITS. INTERIOR | | | FINISHES IN OFFICES SHALL BE CLASS A,B | | | OR C. | | | 2) OCCUPANT LOADS IN BUSINESS | | | OCCUPANCIES IS ONE PERSON PER ONE | | | HUNDRED SQUARE FEET. THE PLAN SEEMS TO | | | SUGGEST A GREATER OCCUPANT LOAD FOR | | | THE SPACE THAN THE CODE ALLOWS. PLEASE | | | EXPLAIN RATIONALE. | | | 3) EXIT SIGN IS TO DIRECT PERSONS TO | | | EXIT DOOR LOCATION IN LOUNGE AREA. | | | 4) STORAGE ROOM DOORS ARE TO BE AT | | | LEAST ONE HOUR FIRE SEPARATED FROM | | | OTHER SPACES BY AT LEAST ONE HOUR IF | | | NO FIRE SPRINKLERS ARE PRESENT. |
|